EasyManuals Logo

Aritech 2X-A Series Installation Manual

Aritech 2X-A Series
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 75
Class B
Select Class B to configure your fire network class configuration (Class A or
Class B). The default setting is NO (Class A network configuration).
To change the network class settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Class B.
3. Select YES (for Class B network) or NO (for Class A network).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Table of Contents

Other manuals for Aritech 2X-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-A Series and is the answer not in the manual?

Aritech 2X-A Series Specifications

General IconGeneral
BrandAritech
Model2X-A Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals