Chapter 3: Configuration and commissioning
74 2X-A Series Installation Manual
Command filter
Select Command filter to configure the types of commands sent to the fire
network in control panels with the corresponding global controls configured.
The commands that can be configured are shown in the table below.
Table 29: Command filter configuration options
Command
Description
RST
Reset
PnSilen
Panel silence
SND
Sounder start/stop
SND_DLY
Sounder delay (enable delay or cancel active delay)
FR
Fire routing start/stop
FR_DLY
Fire routing delay (enable delay or cancel active delay)
FP
Fire protection start/stop
FP_DLY
Fire protection delay (enable delay or cancel active delay)
D/N_M
Day/night mode change [1]
[1] Used to allow control panels within the network to have locally
-defined day/night mode
settings. If this setting is not activated, the control
panel does not send the day/night mode
change and does not process these commands when received from other control panels in the
fire network.
To change the Command filter settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Command filter.
A list of available commands that can be configured is displayed.
3. Select all commands to be filtered.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Table of Contents

Other manuals for Aritech 2X-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-A Series and is the answer not in the manual?

Aritech 2X-A Series Specifications

General IconGeneral
BrandAritech
Model2X-A Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals