Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 73
Repeater map
The default setting is YES (all control panels in the fire network are repeated).
To change the repeater map settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Repeater map.
3. Select the control panel from the list, and then select YES (to repeat the
control panel) or NO (to stop repeating the control panel).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Global controls
Select Global controls to allow the control panel to control the fire network (by
sending global commands defined by the command filter). The default setting is
YES (global commands are allowed).
To change the Global control settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Global controls.
3. Select the control panel from the list, and then select YES (to allow global
control) or NO (to stop global control).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
The commands that can be controlled globally are detailed in Table 29 on page
74.
Event filter
Select Event filter to configure the types of events to repeat from other control
panels in the fire network. The control panel always displays alarm and alert
events. Fault and condition reporting may also be selected if required.
To change the Event filter settings:
1. Select Panel setup from the Main menu.
2. Select Firenet, and then select Event filter.
3. Select the types of events to repeat.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.