Chapter 3: Configuration and commissioning
80 2X-A Series Installation Manual
Buzzer
Select Buzzer to configure the control panel buzzer behaviour (on or off) during
fire alarm, fault, condition, or external connection events. The default setting for
all event types is YES (the buzzer activates).
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Buzzer.
3. Select Alarm, Fault, Cond, or ExtConn, and then select YES or NO.
If NO is selected for Conditions, the buzzer does not activate for External
Connection events (even when the setting for External Connections is YES).
If NO is selected for External Connections, the buzzer does not activate for
External Connection events (even when the setting for Conditions is YES).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Re-sound sounders
Select Re-sound sounders to configure stopped sounder functionality when new
zone alarms are reported. The available configuration options are shown below.
The default setting is YES (sounders re-sound for new zone alarms).
Note: By default, sounders only re-sound for a new alarm (in the same zone) if a
manual call point alarm is reported following a detector alarm.
Table 32: Re-sound sounders configuration options
A new zone in alarm re-sounds the sounders
A new zone in alarm does not re-sound the sounders
If checked, any new device in alarm in the same zone (including
detectors) re-sounds the sounders.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Re-sound sounders.
3. Select YES or NO.
4. Select and check the Device check box if you want any new device in alarm
in the same zone to re-sound the sounders.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.