Chapter 3: Configuration and commissioning
80 2X-A Series Installation Manual
Buzzer
Select Buzzer to configure the control panel buzzer behaviour (on or off) during
fire alarm, fault, condition, or external connection events. The default setting for
all event types is YES (the buzzer activates).
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Buzzer.
3. Select Alarm, Fault, Cond, or ExtConn, and then select YES or NO.
If NO is selected for Conditions, the buzzer does not activate for External
Connection events (even when the setting for External Connections is YES).
If NO is selected for External Connections, the buzzer does not activate for
External Connection events (even when the setting for Conditions is YES).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Re-sound sounders
Select Re-sound sounders to configure stopped sounder functionality when new
zone alarms are reported. The available configuration options are shown below.
The default setting is YES (sounders re-sound for new zone alarms).
Note: By default, sounders only re-sound for a new alarm (in the same zone) if a
manual call point alarm is reported following a detector alarm.
Table 32: Re-sound sounders configuration options
YES (default)
A new zone in alarm re-sounds the sounders
NO
A new zone in alarm does not re-sound the sounders
Device
If checked, any new device in alarm in the same zone (including
detectors) re-sounds the sounders.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Re-sound sounders.
3. Select YES or NO.
4. Select and check the Device check box if you want any new device in alarm
in the same zone to re-sound the sounders.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Table of Contents

Other manuals for Aritech 2X-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-A Series and is the answer not in the manual?

Aritech 2X-A Series Specifications

General IconGeneral
BrandAritech
Model2X-A Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals