Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 81
Self-test
Select Self-test to schedule a functional self-test for each loop device and to
generate a daily report in devices that support this feature. By default self-test is
not enabled.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Self-test.
3. Select and check the Enabled check box.
4. Select TestH, and then enter the start time for the self-test (00:00 to 23:59).
5. Select ReportH, and then enter the time for the report to be generated (00:00
to 23:59).
6. Press F4 (Enter), and then press F1 (Back).
7. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Pulse activation
Select Pulse activation to configure the fire routing output activation pulse time, in
milliseconds, for external devices that require pulsed activation. By default the
output activation is continuous.
This option is not available for repeaters or control panels that do not include fire
routing controls.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Pulse Activation.
3. Select and clear the Contin. check box.
4. Select PulseT, and then enter the pulse time value in milliseconds (0 to
10000).
If the PulseT value is 0, the output activation is continuous.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.