Chapter 3: Configuration and commissioning
2X-A Series Installation Manual 83
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select PSU Supervision.
3. Select and check 10 A or Ext.
Select and check 10 A to enable power supply supervision for large cabinet
control panels with an internal 10 A power supply (-P variants).
Select and check Ext. to enable power supply supervision for any control
panel that is connected to an external power supply.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Note: An incorrect configuration generates a power supply communication fault.
Detector Dirty Warning
Select Det Dirty Warning to configure a detector contamination level, over which
the control panel report a condition for the device. The default setting is 80%.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select Det Dirty Warning.
3. Select Warn_L and enter the required contamination level.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Condition notifications
Select Cond notifications to configure condition logging and notifications (YES or
NO) when new event log entries overwrite older entries. The default setting is
YES (a condition is logged and notifications displayed that new event log entries
overwrite older entries).
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select LogFull.
3. Select LogFull, and then select YES or NO.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Table of Contents

Other manuals for Aritech 2X-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-A Series and is the answer not in the manual?

Aritech 2X-A Series Specifications

General IconGeneral
BrandAritech
Model2X-A Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals