Electromagnetic flowmeter M910
Operation manual
9
Vertical mounting
When the sensor is mounted on a vertical section of pipe, the flow direction must be upwards. In the case of a
downward flow direction, air bubbles can collect in the sensor and the measurement could be unstable and
inaccurate.
Pumps
Never install the sensor on the suction side of a pump or on a section of pipe where a vacuum is possible.