ii FEED PUMP INVERTER DRIVE PARAMETERS
Feed pumps use the IMO Jaguar VXSM drive. All settings are to manufacturer’s
defaults apart from those given below:
Feed pump (gear) Feed pump (cavity)
F01
1 1
F02
1 1
F03
50 100
F11
Full load current from motor nameplate Full load current from motor nameplate
F15
70 100
F30
Adjust so that current displayed on membrane
matches current displayed on inverter
Adjust so that current displayed on membrane
matches current displayed on inverter
F31
2 2
F35
2 2
E34
Full load current from motor nameplate Full load current from motor nameplate
P01
2 4
P02
Power in kW from motor nameplate Power in kW from motor nameplate
P03
Full load current from motor nameplate Full load current from motor nameplate
H21
0 0
53