Motor Error/Safe Mode
Has the valve been reset
(
i.e.
p
owered off
,
then on
)
?
Check
Yes
No
Reset the valve by
powering down & then
p
owerin
g
back on
Are the valve internals free
of debris and clean?
No
Remove valve internals
and thorou
g
hl
y
clean
No
Remove valve internals &
check O-rings/Seals to
ensure they are smooth;
Are the O-Rings/Seals in
good condition & not
preventing the spool travel?
Is the motor operational?
(i.e. is it able to turn/drive
gears?)
Yes
Yes
Yes
Is the magnetic rotor
attached to the motor
operational?
No
Re
p
lace moto
r
No
Check strength of
magnets inside rotor; if
not sufficient, replace
rotor
Yes
Is the valve free of any
leaks coming out of bottom
of valve?
No
Ensure all wires are not
pinched & plugs are
connected; if needed
replace cable loom
Yes
Are supply pressures
nominally equal (within
5psi
)
?
No
E
q
ualize
p
ressures
Yes
Is the valve PCB
operational and ok?
No
Re
p
lace Ele. Housin
g
Yes
Is the valve PSU
operational and ok?
No
Re
p
lace Ele. Housin
g
Yes
Issue addressed or Contact
Factory @ 269-279-3602
Are all cables/wiring &
connectors ok?
Re
p
lace GDA
No
Yes
Key:
PSU = Power Supply GDA = Gear Drive Assembly
PCB = Printed Circuit Board
Yes
No
Is the front electronics
enclosure closed?
Close door fully against
valve bod
y

Questions and Answers: