EasyManua.ls Logo

Arteche CA-36 - INDUCTIVE VOLTAGE TRANSFORMERS;

Default Icon
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
High Voltage Instrument Transformers | CA/UT/KA
User Manual - Annex III
This test verifi es the transformer ratio and polarity, and displays
a “+” signal if correct, and a “-” signal if inverted. To carry out the
test, proceed as follows (Fig. 11).
The excitation terminals (clamps marked “H”) will be
connected to the transformer’s primary terminal:
H1 will be connected to the primary terminal of equipment A.
H2 will be connected to the ground terminal, located at the
base of the equipment.
The clamps marked “X” will be connected to the transformer’s
secondary terminals:
X1 will be connected to 1S1. When the secondary has taps, you
must connect X1 to the tap of the secondary terminal which
is to be tested.
X2 will be connected at the end of the secondary terminal.
This test must be applied to each secondary separately;
in case the transformer has more than 1 secondary, the
secondary(s) which are not to be tested must be left open.
INDUCTIVE VOLTAGE TRANSFORMERS/
Fig. 11
A A

Related product manuals