What to do if Asco 300 Switch doesn't transfer load to emergency source?
- XxbrownAug 5, 2025
If the Asco transfer switch doesn't transfer the load to the emergency source after the generator starts, ensure the generator output circuit breaker is closed and the generator frequency is at least 57 Hz. Wait for the Transfer to Emergency Delay (0 to 5 min.) to time out. For immediate transfer, press the Bypass Time Delay button. If Motor Load Transfer is active, wait for in-phase condition.