P1P1 / P2 / P3 /
Ec / SP / oF
Variable visualized
normally on display:
P1 = measurement
i.dS
19
oFoF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
Time-out ECO mode.
oF = No function
i.tt
18
oFoF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
Delay to Eco mode
with door closed
oF = No function
i.Et
17
oFoF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
Delay in acquiring
digital input
i.ti
16
0 -8 / -7 / -6 / -5 /
-4 / -3 / -2 / -1 /
0 / 1 / 2 / 3 / 4 /
5 / 6 / 7 / 8
Function and function
logic of digital input
di1:
0 = No function
1= Door open
2= Door open with fan
stop
3= Door open with fan
and compressor stop
4= External “AL” alarm
5= External “AL” alarm
with deactivation of
control outputs
6=Selection of active
Set Point (SP-SPE)
7= Switch on/ off
(Stand - by)
8= “Turbo" cycle
activation
i.Fi
15
dGoF / EP / Au /
Pr3 input function:
i.P3
14
EPoF / EP / Au /
dG
Pr2 input function:
oF = No function
EP = evaporator
Au = Aux probe
13
0.0-30.0 ÷ 30.0
°C/°F
Measure offset on the
display
12
0.0-30.0 ÷ 30.0
°C/°F
Pr3 Probe Calibration
11
0.0-30.0 ÷ 30.0
°C/°F
Pr2 Probe Calibration
10
0.0-30.0 ÷ 30.0
Pr1 Probe Calibration
i.C1
9
2.0oF ÷ 20.0
Measurement filter
i.Ft
8
ntPt / nt / P1Probes Type
Pt = PTC
nt = NTC
i.SE
7
C1C0 / F0 / C1 /
F1
Unit of measurement
and resolution
(decimal point)
C0 = °C with 1° res.
F0 = °F with 1° res.
C1 =°C with 0,1° res.
6
0.0S.LS ÷ SP“Turbo” Set Point (or
ind. Heating Set Point
mod. HC )
SPH
5
0.0SP ÷ S.HSEco Set Point
4
0.0S.LS ÷ S.HSSet Point
3
99.9S.LS ÷ 999Maximum Set Point
2
-50.0-99.9 ÷ S.HSMinimum Set Point
1
parameters relative to Set Point
oFoF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
Ritardo compressore
dopo sbrinamento
(sgocciolamento)
d.td
34
20.0oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
Lenght (max.) of
defrost cycle
d.dE
33
oFoF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
Delay start Defrost by
continuous
compressor running
d.cd
32
oFoF - on - LbDefrost display Lock
oF= display free
on= Lock on
temperature Pr1
before defrost
Lb= Lock on label
“dEF” (during
defrosting) and “PdF”
(during
d.dL
31
1.00oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
Delay start Defrost by
"d.tF" start
temperature
d.St
30
-99.9- 99.9 ÷ 999
°C/°F
Defrost start
temperature
29
10.0- 99.9 ÷ 999
°C/°F
Defrost enable
temperature
28
8.0- 99.9 ÷ 999
°C/°F
Defrost stop
temperature
27
parameters relative to defrosting control
oFoF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
Lengh of “turbo” cycle
26
CH / C / nr / HC /
C3
Output operating
mode:
H= Heating
C= Cooling
nr = Neutral Zone
HC =Neutral Zone with
ind. Set point
C3 = Cooling with 3
aut. switch modes
r.HC
25
oFoF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
Output deactivation
time for probe error
24
oFoF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
Output activation time
for probe error
23
2.00.0 ÷ 30.0
°C/°F
Differential
(Hysteresis) in Eco
mode in “turbo” mode
or Heating HC mode.
22
2.00.0 ÷ 30.0
°C/°F
Differential
(Hysteresis) in Eco
mode
r.Ed
21
2.00.0 ÷ 30.0
Differential
r.d
20
r. - parameters relative to temperature control
P2 = measurement
probe Pr2
P3 = measurement
probe Pr3
Ec = Pr1 in normal
mode, Eco in Eco
mode
SP= Active Set Point
oF = Display off
ASCON TECNOLOGIC - Y33 - OPERATING INSTRUCTIONS - Vr. 01 - 04/16 - ISTR-MY33-ENG01 - PAG. 11