PROCALOR HEAT PUMP
19
Water Pump
F40 Water Pump Select
0 – 1
1 -
0: water pump is not enable
1: water pump is enable
F41
Water pump starts time
before compressor starts
1 – 10
3 min
F42
Water pump stops time
after compressor stops
0 – 10
3 min
F43 Water pump stop time
OFF
1 – 99
60 min
F44 Water pump run time
OFF
1 – 10
5 min
Alarm
F50 External alarm mode 3 3 -
3: always closed, unlocked
F59
Buzzer alarm sound
duration
On: Alarm sound is always
on until pressing any key
RTC
F60 Set the RTC time 00:00—23:59 - -
F61 Period 1 start time
05㸸00
-
OFF means not using
F62 Period 1 end time
07㸸00
-
F63 Period 2 start time
OFF
16㸸00
-
F64 Period 2 end time
OFF
18㸸00
-
F65 Period 3 start time
22㸸00
-
F66 Period 3 end time
00㸸00
-
F69 Run Mode 0/1 0 -
0㸸Automatic
1㸸Economical
F80 Password
OFF
0001 -- 9999
OFF -
0000 means clearing
password
System
setting
F81 Temperature unit C/F C -
C:
Centigrade
F: Fahrenheit
F85
running time
- - hour
F86
Accumulative running
time reset
- - -
F87 Probation time
OFF
1 -- 9999
OFF hour
The controller will stop if the
accumulative time is over
probation time, and show the
alarm code “A99”.
OFF means no probation
time
This function can attract all relays in turn, and please don’t use it
when the controller is running!