SMART TDS BLOWDOWN CONTROLLER
5.2 . Changing Function Configurations
5.2.1 Startup Screen
When device is powered, the screen likes the figure on the left.
Then conductivty value, will be seen on the screen of the conrtroller
5.2.2 Enter Commissioning
Hold down button for 5 seconds to enter commissioning mode.
To obstruct unauthorized interferences, BC 900 has password protection.
and buttons change each digit and button passes the next digit.
After change the last digit, button accepts the password and if it is true, it
automatically enters the main menu.
5.2.3 Conductivity Set Point
This function is used to set the conductivity value of blowdown.
Set Point is the TDS level at which the valve will open.
Set point should set in accordance with the
boiler manufacturers recommendations.
For example, 6.000 µS/cm value would be appirate
for fire tube / shell steam boilers.