EasyManua.ls Logo

ATECH BC 900 - Modbus Setup; Password; Default Settings

ATECH BC 900
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMART TDS BLOWDOWN CONTROLLER
5.2.10 Modbus Setup (Optional)
This function is used to set Modbus address baud rate and infrared master/slave
configuration, and verifies the number of units on the IR bus
5.2.11 Password
This function is used to change the password of the device.
Press button to enter to function menu.
and buttons increase or decrease digits and
button shift right to the next digit.
After change the last digit, button accepts the new
password.
It is important that if the default pass code is changed that the new value is noted
and kept safe.
Default password 000
New password
5.2.12 Default Settings
If the default settings are needed, "Default Settings" function could be selected from
the menu.
To select "Default Settings", press button for 5 second on this function.
After confirming "Ok" on the screen, will be returned to the
menu. Default settings as below :
Conductivity Set Point : 5.000 uS/cm
Hysteresis : 300 uS/cm
Alarm : 9.500 uS/cm
Alarm Hysteresis : 300 uS/cm
System Run/Off : System Run
IM-BC900-18C Page 13
BC 900
www.atech-ltd.com

Related product manuals