SMART TDS BLOWDOWN CONTROLLER
5.2.8 System Auto / Off
In this mode can be setted as "System Run" that gives An automatic blowdown or
"System Off" that the timer will give no blowdown.
"System Auto"
This mode gives an automatic blowdown, and is the usual
mode selected.
"System Off"
In this mode, the blowdown controller will give no
blowdown. Automatic blowdown is prevented on this boiler.
5.2.9 Tests outputs (Valve and Alarm)
This function is used to test the Blowdown Control Valve BCV 900 and
the alarm function working properly.
With this function, can be test to open or close the
Blowdown Control Valve.
The valve will be open for 2 minutes. Before the test duration
is finished, when button is pressed the valve will be
closed.
With this function, the alarm relay can be testted.
IM-BC900-18C Page 12