EasyManua.ls Logo

Atlas Copco ZT 55 VSD - Page 76

Atlas Copco ZT 55 VSD
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Install fuses which are smaller than or equal to the Max. fuse values from the technical
data sheets or instruction manual
Size of the PE cable
Use the maximum allowed ampacity of the selected supply cables and compare with
the value in the table below according to UL508A
Ampacity Size of PE
< 90 A 8 AWG
< 125 A 6 AWG
< 150 A 6 AWG
< 200 A 4 AWG
< 225 A 2 AWG
< 400 A 1/0 AWG
< 500 A 1/0 AWG
< 800 A 2/0 AWG
< 1000 A 3/0 AWG
Note: The above table has been prepared for user convenience. Only the latest editions of
the UL standard and its amendment(s) are to be considered as the official documents.
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
Example of supply cable calculation
I
Package
= 128 A, maximum ambient temperature is 30 °C, maximum fuse = 200 A
Single supply cables (3 phases + PE):
I = 128 A + 25 % = 128 x 1.25 = 160 A
For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
So use a cable of 3 x AWG2/0 + AWG4
Parallel supply cable and phase supply cable 2 x (3 phases + PE):
I = (128 A + 25 %)/√3 = (128 x 1.25)/√3 = 93 A
For AWG3, the maximum current is 100 A, which is sufficient => use AWG3
So use a cable of 2x (3 x AWG3 + AWG6)
Parallel phase supply cable 4 x (3 phases + PE):
I = (128 A + 25 %)/(√3 x 2) = (128 x 1.25)/(√3 x 2) = 47 A
For AWG8, the maximum current is 50 A, which is sufficient => use AWG8
So use a cable of 4x (3 x AWG8 + AWG8)
Electric cables
Number of cables: 1x(3+PE) or 2x(3+PE)
Cable type: Cu75/90°C stranded
Wire size range:
Voltage UL Tightening torque
460 V AWG 3/0 17-20 Nm
PE wire maximum size range: 150 mm²
PE wire connection: M10 bolt – tightening torque 32 Nm
Supply voltage tolerance ±10 %
Instruction book
74 API797429

Related product manuals