EasyManua.ls Logo

Atlas Copco ZT-90 - Electric Cables

Atlas Copco ZT-90
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.3 Electric cables
Remarks
The cable sizes below are applicable for the MAINS + EARTH CABLE
The cable size is valid at maximum ambient temperature of 40 ˚C.
The cable size is valid at maximum ambient temperature of 104 ˚F.
50Hz IEC
Pack and Full-Feature compressors
400 V
ZT/ZR55
3 x 50 + 25 mm
2
ZT/ZR75
3 x 95 + 50 mm
2
ZT/ZR90
3 x 120 + 70 mm
2
Full-Feature ND compressors
400 V
ZT/ZR55
3 x 70 + 35 mm
2
ZT/ZR75
3 x 70 + 35 mm
2
ZT/ZR90 2x (3 x 50 + 50
mm)
2
Full-Feature ND compressors
Instruction book
85
380 V 440-460 V
ZT/ZR55
3 x 70 + 35 mm
2
3 x 70 + 35 mm
2
ZT/ZR75 2x (3 x 50+ 35
mm)
2
3 x 70 + 35 mm
2
ZT/ZR90 2x (3 x 70+ 35)
mm
2
2x (3 x 50 + 25
mm)
2

Table of Contents