Installation Manual   2. Installing the Device 
 
2.2.3.2  19-inch Rack Mounting 
The MP-124 can be installed in a standard 19-inch rack, by using two short, equal-length 
brackets (supplied). The MP-124 with attached brackets for rack installation is shown in the 
figure below: 
Figure  2-14: MP-124 with Brackets for Rack Installation 
 
 
 
Rack Mount Safety Instructions 
When installing the chassis in a rack, implement the following safety 
instructions: 
•  Elevated Operating Ambient - If installed in a closed or multi-unit rack 
assembly, the operating ambient temperature of the rack environment 
may be greater than room ambient. Therefore, consideration should be 
given to installing the equipment in an environment compatible with the 
maximum ambient temperature (Tma) of 40°C (104°F). 
•  Reduced Air Flow - Installation of the equipment in a rack should be 
such that the amount of air flow required for safe operation on the 
equipment is not compromised. 
•  Mechanical Loading - Mounting of the equipment in the rack should be 
such that a hazardous condition is not achieved due to uneven 
mechanical loading. 
•  Circuit Overloading - Consideration should be given to the connection 
of the equipment to the supply circuit and the effect that overloading of 
the circuits might have on overcurrent protection and supply wiring. 
Appropriate consideration of equipment nameplate ratings should be 
used when addressing this concern. 
•  Reliable Earthing - Reliable earthing of rack-mounted equipment should 
be maintained. Particular attention should be given to supply connections 
other than direct connections to the branch circuit (e.g., use of power 
strips.) 
 
¾  To install the MP-124 in a 19-inch rack, take these 7 steps: 
1.  Remove the two screws located on one side of the MP-124 (nearest the front panel). 
2.  Insert the peg on one of the brackets into the third air vent down on the column of air 
vents nearest the front panel.