Risk of immediate actuator operation when switching on!
Risk of personal injuries or damage to the valve
Ensure that the ESD COMMAND signal is present when switching on.
If the actuator starts to run unexpectedly: Immediately press push button Stop.
Setting
Settings for the EMERGENCY command are performed via a jumper on the relay
board. For the set EMERGENCY behaviour, refer to the <EMERGENCY command
setting> table
Information The jumper for EMERGENCY command setting is present in the factory as specified
in the order.The wiring diagram pertaining to the order has been coded accordingly
and the connection for the input (terminals XK) has been entered. In case of sub-
sequent change of the setting (rewiring of the jumper), the wiring diagram will no
longer correspond to the changed settings. For this reason, setting changes may
exclusively be performed by the AUMA service.
Figure 33: Relay board
Table 12: EMERGENCY command setting
EMERGENCY command (EMERGENCY behaviour)Link [B9]
EMERGENCY - CLOSE (Actuator runs to end position CLOSED.)
EMERGENCY - OPEN (Actuator runs to end position OPEN.)
10.8. Controls: close
Danger of corrosion due to damage to paint finish!
Touch up damage to paint finish after work on the device.
1. Clean sealing faces of housing and cover.
2. Check whether O-ring [3] is in good condition, replace if damaged.
43
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2
AMB 01.1 Commissioning controls settings