AUTEC - Air series
Malfunction signalled by the receiving unit 7
LIRMGE00-01
8 Malfunction signalled by the receiving unit
Use the light signals on the receiving unit to identify the radio remote control malfunction.
If the problem persists after the suggested solution has been carried out, contact the support
service of the machine manufacturer.
Signals Possible reason Solutions
The POWER LED is o󰓐.
Wrong or no power
supply.
Correctly plug in the connecting plug
between the radio remote control and
the machine.
Make sure that power supply wires are
correctly connected and that the power
supply value is within the limits speci󰘰ed
in the technical data.
Check the power supply protection fuse
and, if needed, replace it.
The POWER LED is
steady and the ENABLE
LED blinks once every 5
seconds.
The transmitting and
receiving unit do not
communicate.
Start up the radio remote control.
The POWER LED is
steady and the ENABLE
LED blinks fast.
The receiving unit does
not activate the outputs of
the commands sent.
Check that the outputs are correctly
wired and that the commands sent
activate the corresponding relays.
Check the protection fuses of the STOP
contacts or of the SAFETY contacts and,
if needed, replace them.