5–9
Parameter Memory Addresses (continued)
Parameter Description Hexadecimal
Modbus
Decimal *
Octal
Communications Parameters
P9.00
Communication Address 0900 42305 4400
P9.01
Transmission Speed 0901 42306 4401
P9.02
Communication Protocol 0902 42307 4402
P9.03
Transmission Fault Treatment 0903 42308 4403
P9.04
Time Out Detection 0904 42309 4404
P9.05
Time Out Duration 0905 42310 4405
P9.07
Parameter Lock 0907 42312 4407
P9.08
Restore to Default 0908 42313 4410
P9.11
Block Transfer Parameter 1 090B 42316 4413
P9.12
Block Transfer Parameter 2 090C 42317 4414
P9.13
Block Transfer Parameter 3 090D 42318 4415
P9.14
Block Transfer Parameter 4 090E 42319 4416
P9.15
Block Transfer Parameter 5 090F 42320 4417
P9.16
Block Transfer Parameter 6 0910 42321 4420
P9.17
Block Transfer Parameter 7 0911 42322 4421
P9.18
Block Transfer Parameter 8 0912 42323 4422
P9.19
Block Transfer Parameter 9 0913 42324 4423
P9.20
Block Transfer Parameter 10 0914 42325 4424
P9.21
Block Transfer Parameter 11 0915 42326 4425
P9.22
Block Transfer Parameter 12 0916 42327 4426
P9.23
Block Transfer Parameter 13 0917 42328 4427
P9.24
Block Transfer Parameter 14 0918 42329 4430
P9.25
Block Transfer Parameter 15 0919 42330 4431
P9.26
Serial Comm (RS-485) Speed Reference 091A 42331 4432
P9.27
Serial Comm RUN Command 091B 42332 4433
P9.28
Serial Comm Direction Command 091C 42333 4434
P9.29
Serial Comm External Fault 091D 42334 4435
P9.30
Serial Comm Fault Reset 091E 42335 4436
P9.31
Serial Comm JOG Command 091F 42336 4437
P9.39**
Firmware Version 0927 42344 4447
P9.40
Parameter Copy 0928 42345 4450
P9.41
GS Series Number 0929 42346 4451
P9.42
Manufacturer Model Information 092A 42347 4452
* For Modbus Decimal addresses used with CLICK PLCs,
insert another zero as the next-to-most-significant digit, e.g., 402333 instead of 42333.
** Some parameters are available only in later firmware versions of DURAPULSE drives.
Refer to P9.39 and “DURA
PULSE Parameter Summary” in Chapter 4 for more information.
Parameter can be set during RUN Mode..
Chapter 5: DURAPULSE MODBUS Communications
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013