4–5
Parameter Summary (continued)
Parameter
*
Description Range*
Default
Setting
User
Setting
Digital Parameters
P3.00
Source of
Operation Command
00: Operation determined by digital keypad
01: Operation determined by external control
terminals; keypad STOP is enabled
02: Operation determined by external control
terminals; keypad STOP is disabled
03: Operation determined by RS-485
interface; keypad STOP is enabled
04: Operation determined by RS-485
interface; keypad STOP is disabled
00
P3.01
Multi-function Input Terminals
(DI1 - DI2)
00: DI1 - FWD / STOP, DI2 - REV / STOP
01: DI1 - RUN / STOP, DI2 - REV / FWD
02: DI1 - RUN momentary (N.O.)
DI2 - REV / FWD
DI3 - STOP momentary (N.C.)
00
P3.02
Multi-function Input DI3
00: External Fault (N.O.)
01: External Fault (N.C.)
02: External Reset
03: Multi-Speed Bit 1
04: Multi-Speed Bit 2
05: Multi-Speed Bit 3
06: Multi-Speed Bit 4
07: Manual Keyboard Control
08: Reserved
09: Jog
10: External Base Block (N.O.)
11: External Base Block (N.C.)
12: Second Accel/Decel Time
13: Speed Hold
14: Increase Speed
15: Decrease Speed
16: Reset Speed to Zero
17: PID Disable (N.O.)
18: PID Disable (N.C.)
19: 1st/2nd Source Select (N.O.)
20: 1st/2nd Source Select (N.C.)
99: Input Disable
00
P3.03
Multi-function Input DI4 03
P3.04
Multi-function Input DI5 04
P3.05
Multi-function Input DI6 05
P3.06
Multi-function Input DI7 06
P3.07
Multi-function Input DI8 09
P3.08
Multi-function Input DI9 02
P3.09
Multi-function Input DI10 12
P3.10
Multi-function Input DI11 10
* Some parameters and settings are available only in later firmware versions of DURAPULSE drives. Refer to
the beginning of this “DURA
PULSE Parameter Summary” section for more information.
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013