Chapter 4: AC Drive Parameters
4–6
Parameter Summary (continued)
Parameter
*
Description Range*
Default
Setting
User
Setting
Digital Parameters (continued)
P3.11
Multi-Function
Output Terminal 1
(Relay Output)
00: AC Drive Running
01: AC Drive Fault
02: At Speed
03: Zero Speed
04: Above Desired Frequency (P3.16)
05: Below Desired Frequency (P3.16)
06: At Maximum Speed (P0.04)
07: Over Torque detected (P6.08)
08: Above Desired Current (P3.17)
09: Below Desired Current( P3.17)
10: PID Deviation Alarm
11: Heatsink Overheat Warning (OH1)
12: Soft Braking Signal
13: Above Desired Frequency 2 (P3.20)
14: Below Desired Frequency 2 (P3.20)
15: Encoder Loss
16: PID Feedback Loss Warning
00
P3.12
Multi-Function
Output Terminal 2
(DO1)
01
P3.13
Multi-Function
Output Terminal 3
(DO2)
02
P3.14
Multi-Function
Output Terminal 4
(DO3)
03
P3.16
Desired Frequency 0.0 to 400.0 Hz 0.0
P3.17
Desired Current 0.0 to <Drive Rated Amps> 0.0
P3.18
PID Deviation Level 1.0 to 50.0 % 10.0
P3.19
PID Deviation Time 0.1 to 300.0 sec 5.0
P3.20
Desired Frequency 2 0.0 to 400.0 Hz 0.0
P3.30
Frequency Output (FO)
Scaling Factor
1 to 20 1
P3.31
2nd Source of
Operation Command
00: Operation determined by digital keypad
01: Operation determined by external
control terminals; keypad STOP is
enabled
02: Operation determined by external
control terminals; keypad STOP is
disabled
03: Operation determined by RS-485
interface; keypad STOP is enabled
04: Operation determined by RS-485
interface; keypad STOP is disabled
0
* Some parameters and settings are available only in later firmware versions of DURAPULSE drives. Refer to
the beginning of this “DURA
PULSE Parameter Summary” section for more information.
Parameter can be set during RUN Mode.
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013