Page 2–18 SureServo2 User Manual – 1st Edition – 05/20/2021
Chapter 2: Installation
Monitoring DI/DO Codes ParametersAlarms Wiring
DOX-
Servo drive
DOX+
DO1(7,6)
DO2(5,4)
DO3(3,2)
DO4(1,26)
DO5(28,27)
DO6(46,40)
DOX(DOX+,DOX-)
X=1,2,3,4,5,6
Ensure the polarity of
diode is correct, or it
will damage the drive
DC24V
Relay
DC24V
For brake
It is open circuit when the
emergency stop signal is on.
Brake 1 (blue)
Brake 2 (brown)
Motor
Brake
Encoder
Notes:
Please refer to Chapter 3 Wiring�
Please use relay part number 781-1C-24D or equivalent�
Please use diode part number AD-ASMD-250 or equivalent�
The brake signal controls the solenoid, providing power to the brake and enabling the brake�
Please note that there is no polarity for the coil brake� DC+ and DC- voltage can be
connected to either the blue or brown wires�
Timing diagram of control power and main power:
1 sec
2 sec
> 0 ms
800 ms
Can be input
1 ms (Min. value)+ Delay time of the digital filter (P2.009)
L1c, L2c
Control power
5 V
Control power
RST
Main circuit power
BUS voltage
ready
Servo ready
Servo on
(DI)
Servo on
(DO)
Position/Speed/Torque
command input
Calculating the brake’s rated current (SV2L-204N is used as an example here).
Power consumption of the brake (20°C) = 6.5 W (refer to Appendix A Motor specifications),
so the brake’s rated current = (6.5 W)/24V = 0.27 A.