8 Timer Mode
© Copyright Reserved Autonics Co., Ltd. 67
On Time
Display
[ONtD]
When memory protection setting is OFF
※ON time indicate mode of INA input
1) Time reset start operates when INA input turns ON.
2) Time progress stops while INA input is OFF.
3) When time progress stops and power is off, the display value is initialized.
4) If progress time is greater than setting time when INA input turns off,
display value flashes and operation stops until reset signal is applied.
When memory protection setting is ON
※ ON time indicate mode of INA input
1) Time reset start operates when INA input turns ON.
2) Time progress stops while INA input is OFF.
3) When time progress stops and power is off, the display value is memorized.
4) If progress time is greater than setting time when INA input turns off,
display value flashes and operation stops until reset signal is applied.
※TMR mark flashes during timer operating.
※TMR mark turn ON for timer stop or hold.
※The present value is zero blank format for highest unit.
E.g.)In case of time range is 99m59.99s and the present value is 00m04.05s, zero blank is
applied for the highest unit, minute. In case of the below digit of decimal point, zero blank
is not applied. Therefore, it displays “0.0$05”.
※In case of timer, it is available for PRESET to set as ‘0’ and the output operates.