Pressure  Static 
 0.1 kPa  0.1 kPa  1 kPa 0.1 kPa 
       
MPa - - 0.001 - 0.001 - - -
kPa 0.1 - 0.1 - 1 - - 0.1
2
0.001 - 0.001 - 0.01 - - 0.001
bar 0.001 - 0.001 - 0.01 - - 0.001
 - 0.01 - 0.01 - 0.1 - 0.02
 - 0.4 - 0.8
 - 0.02 - 0.03
mmH
2
O 
0.1 - - 0.1
 01)   Multiply display value by 100.
Model
PSAN-
PSAN-
PSAN-
Pneumatic type model: Gauge pressure
Fluid type model: Gauge pressure 
 01)
 or sealed gauge pressure 
 02)
Pressure Negative Static Compound
 0.1 kPa  0.1 kPa  1 kPa 0.1 kPa 
0.0 to -101.3 
kPa
0.0 to 100.0 
kPa
0 to 1,000 kPa
-101.3 to 100.0 
kPa
5.0 to -101.3 
kPa
-5.0 to 110.0 
kPa
-101.3 to 1,100 kPa
-101.3 to 110.0 
kPa
 7 Segment LED, 4 ½ digit
 -10 to 0 ℃: ≤ ±1% F.S., 0 to 50 ℃: ≤ ±0.5% F.S.
Rated pressure 
×2
Rated 
pressure ×2
•  Pneumatic type: 
Rated pressure ×1.5
•  Fluid type: Rated 
pressure ×2
Rated pressure 
×2
 01)   Only for static pressure, rated pressure range 100.0 kPa model
 02)  The unit is sealed structure. It is based on atmospheric pressure 101.3 kPa.
medium
 
 Connector type Cable type / connector type
Cable Ø 4 mm, 5-core, 2 m
Connector type: Ø 4 mm, 5-core, 2 m
Cable type: Ø 4 mm, 5-core, 3 m
 AWG24 (0.08 mm, 40-core), insulator diameter: Ø 1 mm
Material
Front case: PC 
Back case:  (back port) PC /  
(bottom port) PBT+GF15% 
Pressure port: Brass-nickel plated
Front case: PC 
Back case: PA6 
Pressure port: SUS304/SUS316L
Protection 
structure 
Connector type: IP40 (IEC standard)
Connector type: IP40 (IEC standard)
Cable type: IP65 (IEC standard)
 ᜢ  ᜫ
Back port: ≈ 80 g (≈ 165 g)
Bottom port: ≈ 85 g (≈ 170 g)
Connector type: ≈ 88 g (≈ 173 g)
Cable type: ≈ 90 g (≈ 167 g)
 12 - 24 VDCᜡ (ripple P-P: ≤ 10%)
90 to 110% of rated voltage
 ≤ 50 mA 
 01)
 NPN open collector output / PNP open collector output model
Load voltage ≤ 30 VDCᜡ
Load current ≤ 100 mA
Residual voltage NPN: ≤ 1 VDCᜡ, PNP: ≤ 2 VDCᜡ
Hysteresis According to output operation mode 
 02)
Repeat error ±0.2% F.S. ±min display interval
Response time 2.5, 5, 100, 500, 1000 ms
Protection circuit Output short over-current protection circuit
Insulation resistance  ≥ 50 MΩ (500 VDCᜡ megger)
Between the charging part and the case: 1,000 VACᜠ 50 / 60 Hz for 1 min
Vibration 
1.5 mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction 
for 2 hours
 -10 to 50 ℃, Storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity 30 to 80%RH, Storage: 30 to 80%RH (no freezing or condensation)
 01)   Current output: ≤ 75 mA
 02)   Refer to 'Output operation mode'. ±1digit error may occur due to pressure unit operation.
  
Output impedance 1 kΩ -
Linearity ≤ ±1% F.S ≤ ±1% F.S
Zero-point ≤ 1 VDCᜡ ±2% F.S. ≤ DC 4 mA ±2% F.S.
Span ≤ 4 VDCᜡ ±2% F.S. ≤ DC 16 mA ±2% F.S.
Resolution 1/1000 or 1/2000 (dierent by pressure type and display unit)
Response time 50 ms 70 ms
[M] for over 3 sec 
 
[M] for over 3 sec 
[M] 
[M] 
[▼]+[▲] for over 1 
sec after remove the 
external pressure
adjustment
Displays 0.0 and 
returns automatically
[▲] for over 3 sec 
[M]
Reset or set: [▼]+[▲] 
for over 1 sec
 01)   Max. / Min. pressure value is available to check by monitoring.  
[Option external input model] Auto shift judgment level checking / setting is available when P-9 External input 
terminal is set as SHFT. (no input displays 0)
• Some parameter are activated / deactivated depending on other parameters. Refer to 
the description.
• The setting item name and setting value are cross-displayed on the display part. 
• It returns to RUN mode when there is no additional key input for 60 sec in each 
parameter group.
• Guaranteed write life: 100,000 times
• [M] key: Saves setting value and moves to next parameter 
[▼], [▲
] key: Selects setting value
Parameter  Default 
P-1 Display unit UNIT
KPA
[Negative / Compound pressure model]
kPa, KGC: kgf/cm
2
, bar, psi, mmHg, inHg, H2O: mmH
2
O
MPA
[Static pressure model]
MPa, kPa, KGC: kgf/cm
2
, bar, psi
P-2
OUT 
operation 
mode
OUtM OFF
HYS.M: Hysteresis 
WIN: Window comparison output 
HY-W: Hysteresis-Window comparison output
AUTO: Auto sensitivity setting
F.OUT: Forced output control 
P-3 Output type NoNC 1O2O
OUT1 OUT2
1O2O Normally open Normally open 
1O2C Normally closed Normally open
1C2O Normally closed Normally open
1C2C Normally closed Normally closed
P-4
Response 
time
SPD @5 2.5, 5.0, 100, 500, 1,000 ms
P-5
Voltage low 
limit scale
A-1V )0
[Option voltage output model]
Min. rated pressure ≤ Low limit scale ≤ 90% of rated 
pressure 
P-6
Voltage high 
limit scale
A-5V 10)0
[Option voltage output model]
Low limit scale setting value + 10% of rated pressure  
≤ High limit scale ≤ Max. rated pressure
P-7
Current low 
limit scale
A-04 )0
[Option current output model]
Min. rated pressure ≤ Low limit scale ≤ 90% of rated 
pressure 
P-8
Current high 
limit scale
A-20 10)0
[Option current output model]
Low limit scale setting value +10% of rated pressure  ≤ 
High limit scale ≤ Max. rated pressure
P-9
External 
input 
terminal
D-IN HOLD
[Option external input model]
HOLD: Hold
SHFT: Auto shift
P-10
Auto shift 
output
 01)
ShOT OUT1
[Option external input model]
OUT1, OUT2, ALL
P-11 Lock LOCK LOC1
LOC1:  Parameter, preset, zero-point adjustment setting 
lock / Monitoring value reset lock 
LOC2: Parameter lock (available to check setting value)
OFF
 01)   Condition: P-9. External input terminal SHFT setting