H-61
Economical PID Control
(A) 
Photoelectric 
Sensors
(B) 
Fiber
Optic
Sensors
(C) 
Door/Area
Sensors
(D) 
Proximity
Sensors 
(E) 
Pressure
Sensors 
(F) 
Rotary
Encoders 
(G) 
Connectors/
Sockets 
(H)
Temperature
Controllers
(I)
SSRs / Power
Controllers
(J) 
Counters 
(K) 
Timers
(L) 
Panel
Meters 
(M)
Tacho /
Speed / Pulse
Meters 
(N)
Display
Units
(O)
Sensor
Controllers 
(P)
Switching
Mode Power
Supplies 
(Q)
Stepper Motors 
& Drivers 
& Controllers
(R)
Graphic/
Logic
Panels
(S)
Field
Network
Devices
(T) 
Software
※
In case of changing input 
sensor type [
IN-T
], it changes 
automatically as max./min. value 
of the changed input sensor. 
※
For indicator model (TC4
-N N), 
only 
OFF
, 
LOC1
 are available.
※
Operates only selected output between Relay or SSR.
※
When changing control output operation, 
ErMU 
is initialized.
※
When changing control type, 
ErMU 
is initialized (control output 
MV is below 100%) and
 DI-K 
turns OFF automatically.
※
It is displayed when selecting control output [
OUT
] as 
SSR
. 
For AC/DC power type (TC4
- 2R), this parameter [
SSrM
] 
is not displayed.
※
Press 
 key to convert alarm 
operation mode into alarm option.
※
Refer to page H-62.
※
Same with the above [
AL-1
].
※WhenchangingalarmoperationAL1,AL2alarmtemperatureof
AL1,AL2isinitialized.
Setting range:0.5 to 120.0 sec.
※
If control output [
OUT
] is set as 
RLY
, factory default is 20.0 sec, or set as SSR drive output 
[
SSR
], factory default is 2.0 sec. 
※This
T
willnotbedisplayedwhenSSRdriveoutputmethod
 [
SSrM
] is set as 
CYCL
, 
PHAS
.
Setting range: 1 to 100
℃/℉
 (
DPtL
/
 CYsL
: 0.1 to 50.0
℃
)
※
If AL1, AL2 alarm operation [
AL-1
,
 AL-2
] is set to 
AM)_
, 
SBa
, 
LBA
, 
AHYS
 parameter is 
not displayed.
Setting range: 0.0 to 100.0%
※
0.0/100.0% is displayed when control type parameter [
C-MD
] is set 
ONOF
.
※WhenchangingPIDcontroltoON/OFFcontrol,ifMVisbelow100.0%,itisinitializedas0.0%.
※
AlRE
isnotdisplayedfornotalarmoutputmodel.
※
AT
isnotdisplayedwhencontroltypeparameter[
C-MD
]isset
ONOF
.
Setting range: 0 to 9999sec. (Automatically setting with Auto-tuning)
※
LBaT
 parameter is displayed when AL1, AL2 alarm operation [
AL-1
, 
AL-2
] is set as 
LBA
.
Setting range: 0 to 999
℃/℉(
DPtL
/ 
CUs
: 0.0 to 999.9
℃/℉
)
(automatically setting with auto-tuning)
※
When alarm operation mode [
AL-1
, 
AL-2
] is set as loop break alarm (LBA) [
LBA
], and 
LBaT
 parameter does not set as 0, 
LBaB
 parameter is displayed.
Setting range:  Within the rated temperature range by 
input sensor [
L-SV 
≤ (
H-SV
-1digit)]
※
When changing SV low-limit value, if SV<
L-SV
, SV is 
initialized as 
L-SV
.
Setting range:  Within the rated temperature range by 
input sensor [
H-SV 
≥ (
L-SV
+1digit)]
※
When changing SV high-limit value, if SV>
H-SV
,
 SV is 
initialized as 
H-SV
.
SV low-limit value
SV high-limit value
Control output operation
Control type
Control output type
SSR dirve output method
Control cycle
AL1 alarm operation
AL2 alarm operation
Alarm output hysteresis
LBA monitoring time
LBA detection band
Digital input key 
Control output MV in case
of input break error
Parameter lock
※
Alarm operation
※
Alarm option
L-SV
H-SV
O-FT
C-MD
OUT
LOC OFF LOC1 LOC2 LOC3
ErMV 00)0
DI-K
002
0
00I
AM@A
SSrM
T
AL-1
AL-2
AHYS
LBaT
LBaB
-050
1200
HEAT
PID
RLY
STND
02)0
AMiA LBaA
AM!A AMiB
COOL
ONOF
SSR
CYCL PHAS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
STOPOFF AlRE AT
Press   +   keys for 3 sec. and it executes 
the set function. For more information, refer to 
 
Functions ' 
Digital input key'.