H-54
TC Series
Features
Economical Single Display Type, PID Control
Ordering Information
Specifications
Series TC4S TC4SP TC4Y TC4M TC4W TC4H TC4L
Power
supply
AC power 100-240VAC 50/60Hz
AC/DC power 24VAC 50/60Hz, 24-48VDC
Allowable voltage range 90 to 110% of rated voltage
Power
consumption
AC power Max. 5VA (100-240VAC 50/60Hz)
AC/DC power Max. 5VA (24VAC 50/60Hz), Max. 3W (24-48VDC)
Display method 7Segment (red), Other display (green, yellow, red) LED
Character size (W×H) 7.0×15.0
mm
7.4×15.0
mm
9.5×20.0
mm
9.5×20.0
mm
7.0×14.6
mm
11.0×22.0
mm
Input type
RTD DPt100Ω, Cu50Ω (allowable line resistance max. 5Ω per a wire)
Thermocouple K (CA), J (IC), L (IC)
Display
accuracy
※
1
RTD
At room temperature (23
℃
±5
℃
): (PV ±0.5% or ±1
℃
, select the higher one) ±1digit
Out of room temperature range: (PV ±0.5% or ±2
℃
, select the higher one) ±1digit
※
For TC4SP, add ±1
℃
by accuracy standard.
Thermocouple
※1:IncaseoftheACvoltagemodel,SSRdriveoutputmethod(standardON/OFFcontrol,cycle,control,phasecontrol)isavailableto
select.
※
2: It is unavailable for TC4SP, TC4Y.
※
3: 11-pin socket (PG-11, PS-11(N)) for TC4SP: sold separately.
● Realizes ideal temp. controlling with newly developed
PID control algorithm and 100ms high speed sampling
● Built-in relay output or SSR output selectable
: Enables to phase control and cycle control
with SSR drive output (SSRP function)
● Dramatically increased visibility using wide
display part
● Mounting space saving with compact design
: Approx. 38% reduced size compared with
existing model (depth-based)
● SV/PV deviation indicatable
Setting type
Item
Digit
Size
Alarm output
Power supply
Control output
N Indicator - Without control output
R Relay output + SSR drive output
※
1
2 24VAC 50/60Hz, 24-48VDC
4 100-240VAC 50/60Hz
N No alarm output
1 Alarm 1 output
2 Alarm 1 output + Alarm 2 output
※
2
S DIN W48×H48mm (Terminal block type)
SP DIN W48×H48mm (11-pin plug type)
※
3
Y DIN W72×H36mm
M DIN W72×H72mm
H DIN W48×H96mm
W DIN W96×H48mm
L DIN W96×H96mm
4 9999 (4digit)
C Set by touch switch
T Temperature controller
T S 1 4 R4C
※
1: Thermocouple L (IC) type, RTD Cu50Ω
At room temperature (23
℃
±5
℃
)
:
(PV ±0.5% or ±2
℃,selectthe
higher one) ±1digit
Out of room temperature range:
(PV ±0.5% or ±3
℃,selectthe
higher one) ±1digit
In case of TC4SP Series, ±1
℃
will be added.