TC Series
Features
Economical Single Display Type, PID Control
Ordering Information
Specifications
Series TC4S TC4SP TC4Y TC4M TC4W TC4H TC4L
Power
supply
AC power 100-240VAC 50/60Hz
AC/DC power 24VAC 50/60Hz, 24-48VDC
Allowable voltage range 90 to 110% of rated voltage
Power
consumption
AC power Max. 5VA (100-240VAC 50/60Hz)
AC/DC power Max. 5VA (24VAC 50/60Hz), Max. 3W (24-48VDC)
Display method 7Segment (red), Other display (green, yellow, red) LED
Character size (W×H) 7.0×15.0
mm
7.4×15.0
mm
9.5×20.0
mm
9.5×20.0
mm
7.0×14.6
mm
11.0×22.0
mm
Input type
RTD DPt100Ω, Cu50Ω (allowable line resistance max. 5Ω per a wire)
Thermocouple K (CA), J (IC), L (IC)
Display
accuracy
1
RTD
At room temperature (23
±5
): (PV ±0.5% or ±1
, select the higher one) ±1digit
Out of room temperature range: (PV ±0.5% or ±2
, select the higher one) ±1digit
For TC4SP, add ±1
by accuracy standard.
Thermocouple
※1:IncaseoftheACvoltagemodel,SSRdriveoutputmethod(standardON/OFFcontrol,cycle,control,phasecontrol)isavailableto
select.
2: It is unavailable for TC4SP, TC4Y.
3: 11-pin socket (PG-11, PS-11(N)) for TC4SP: sold separately.
● Realizes ideal temp. controlling with newly developed
PID control algorithm and 100ms high speed sampling
Built-in relay output or SSR output selectable
: Enables to phase control and cycle control
with SSR drive output (SSRP function)
● Dramatically increased visibility using wide
display part
● Mounting space saving with compact design
: Approx. 38% reduced size compared with
existing model (depth-based)
● SV/PV deviation indicatable
Setting type
Item
Digit
Size
Alarm output
Power supply
Control output
N Indicator - Without control output
R Relay output + SSR drive output
1
2 24VAC 50/60Hz, 24-48VDC
4 100-240VAC 50/60Hz
N No alarm output
1 Alarm 1 output
2 Alarm 1 output + Alarm 2 output
2
S DIN W48×H48mm (Terminal block type)
SP DIN W48×H48mm (11-pin plug type)
3
Y DIN W72×H36mm
M DIN W72×H72mm
H DIN W48×H96mm
W DIN W96×H48mm
L DIN W96×H96mm
4 9999 (4digit)
C Set by touch switch
T Temperature controller
T S 1 4 R4C
1: Thermocouple L (IC) type, RTD Cu50Ω
At room temperature (23
±5
)
:
(PV ±0.5% or ±2
℃,selectthe
higher one) ±1digit
Out of room temperature range:
(PV ±0.5% or ±3
℃,selectthe
higher one) ±1digit
In case of TC4SP Series, ±1
will be added.

Other manuals for Autonics TC4M

Question and Answer IconNeed help?

Do you have a question about the Autonics TC4M and is the answer not in the manual?

Autonics TC4M Specifications

General IconGeneral
BrandAutonics
ModelTC4M
CategoryController
LanguageEnglish

Summary

TC Series Specifications Overview

TC Series Parameter Groups

TC Series Functions and Alarms

Alarm Operation Modes and Options

Explains different alarm operation modes (deviation, absolute value) and alarm options (latch, sequence).

Sensor Break and Loop Break Alarms

Details the functions for sensor break alarm and loop break alarm (LBA).

TC Series Advanced Control Features

Loop Break Alarm (LBA) Operation

Describes how the Loop Break Alarm (LBA) checks control loop stability.

SSR Drive Output Modes

Explains the SSRP function for standard, cycle, and phase control using SSR drive output.

TC Series Control Modes and Tuning

Control Mode Selection

Details ON/OFF, Cycle, and Phase control modes for load control.

Auto Tuning and Input Correction

Explains the Auto Tuning function and input correction/digital filter settings.

TC Series Output Connections and Usage Precautions