TC Series
Parameter Group 1
Parameter Group 2
Setting range: Deviation alarm (- [F.S] to [F.S], Absolute value alarm (temperature range)
※
In case alarm operation mode [
AL-1
,
AL-2
],
AM)_
/
SBa
/
LBa
of parameter group
2 is set to [
AL-1
,
AL-2
], no parameters is displayed.
※
It starts to operate auto-tuning when it is ON and set as OFF automatically
after finish the operation.
※
Deviation indicators (▲, ■, ▼) flash (cycle:1 sec.) during auto tuning
function.
Setting range: 0.1 to 999.9
℃/℉
Setting range: 0 to 9999 sec.
※
Integral operation will be OFF when set value is "0".
Setting range: 0 to 9999 sec.
※
Derivative operation will be OFF when set value is "0".
Setting range: 0.0 to 100.0%
※
It is displayed in P/PD control.
Setting range: 1 to 100
℃/℉(
0.1 to 50.0
℃/℉)
※
It is displayed when control type parameter [
C-MD
] of parameter group 2 is set
ONOF
.
※
1:
S
: Press any key among , , .
※
2: After checking/changing set value at each parameter, and press
key, set value
flashes twice and it moves to next parameter automatically.
※
3: It is displayed when control type parameter [
C-MD
] of parameter 2group is set
PID
.
※
Press
key for 3 sec. to return RUN mode at any parameter.
※
This parameter might not be displayed depending on other parameter settings.
AL1 alarm temperature
AL2 alarm temperature
Auto-tuning
Proportional band
Integral time
Derivation time
Manual reset
Hysteresis
Run mode
※
1
※
3
PAR1
AL1
AL2
AT
P
1
D
REST
HYS
1250
1250
OFF ON
01)0
0000
0000
05)0
002
S
S
S
S
S
S
S
S
2 sec.
3 sec.
※
2
Setting range: -999 to 999 (
DPtL
/
CUsL
: -199.9 to 999.9)
Setting range: 0.1 to 120.0 sec.
※
Set input digital filter time for average input value affected control, and display value.
※
Front temperature unit indicator will flash when selecting the unit.
※
When changing input type SV
IN-B
,
H-SV
,
L-SV
,
AL1
,
AL2
,
LBaT
,
LBaB
,
AHYS
parameters are initialized.
※
When changing input type SV
IN-B
,
H-SV
,
L-SV
,
AL1
,
AL2
,
LBaT
,
LBaB
,
AHYS
parameters are initialized.
Input type
Temperature unit
Input correction
Input digital lter
※
1
PAR2
IN-T KCA
CUsL CUsH DPtL
JIC LIC
DPtH
UNIT ?C ?F
IN-B 000
MAvF )1
S
S
S
S
Run mode
4 sec.
3 sec.
※
2
※
1:
S
: Press any key among , , .
※
2: After checking/changing set value at each parameter, and press
key, set value
flashes twice and it moves to next parameter automatically.
※
Press
key for 3 sec. to return RUN mode at any parameter.
※
This parameter might not be displayed depending on other parameter settings.