AUX-DC inverter ARV outdoor unit individual series technical manual
91
The installation location should be easy for drainage;
It shouldn’t be installed in places (such as kitchen, laundry and mechanical workshop, etc.) of heat
source, vapor source and more oil mist to prevent degradation of heat exchanger, electric shock and
unit damage caused by plastic parts corrosion;
Install in the place at least 1m away from TV and radio to prevent interfering TV and radio.
There should be certain space between the surrounding and outdoor unit for maintenance.
The unit must be well ventilated if installed in closed room. In case of refrigerant leakage,
immediately stop the system, timely contact maintenance personnel and avoid fire on site.
Tool
Application
R410A
Reasons
Pipe cutter
cutting tube
——
Flaring tool
flaring tube and
flaring opening when
welding
It’s required to increase extension allowance of
copper tube when using R410A.
Tube bender
bending tube
——
Torque
wrench
tightening flare nut
The torque of 1/2 and 5/8 is increased and torque
reference is changed
Welding
torch, 2B
silver solder
welding tube
——
Oxygen,
acetylene
——
Nitrogen
Prevent the oxidation of the copper pipe while welding
Vacuum
pump with
return flow
stop valve
(pumping
speed4L/S)
Vacuum piping
system
Don’t use original vacuum pump. It must be ensured
that the oil in vacuum pump can’t flow into A/C
system.
Refrigerant
holder
dosing of refrigerant
charge
R410A should be charged in liquid state.
Electronic
scale
——
Pressure
gauge
inspection equipment
refrigerant pressure
while vacuuming,
charging ,running
The old pressure gauge can’t be used due to the need
of different pressure.
MAX: HP5.3Mpa LP3.5Mpa
Connecting
hose
Leak detector
Checking the leakage
of system
Don’t use Freon leak detector of CFCs or HCFCs,
because there is no chlorine in new refrigerant. It’s
necessary to use hydrogen leak detector or R134a
leak detector.
Note: universal ▲special for R410A