- Appropriate rack space to accommodate 1U switch height is 1.7 inches (44 millimeters).
- Four-post rack bolted to floor and braced if necessary.
- Four post-rack must be grounded to the same grounding electrode used by the power
service in the area. The ground path must be permanent and must not exceed 1 ohm of
resistance from the rack to the grounding electrode.
Figure 8: Four-post rack-mount kit assembly
Procedure
1. Attach a front bracket to each guide bracket with four 8.5 mm length flat head machine
screws.
2. Attach the guide brackets to the switch chassis.
Switch installation
February 2016 Installing Avaya Ethernet Routing Switch 4900 Series 31