Chapter 6.
MAINTENANCE AND INSPECTION
WARNING
Before mounting, removing, or wiring this device, be sure to turn OFF the power
to the module and any connected devices. Failure to do so may result in an elec
-
tric shock.
Do not touch terminals F or G on this device or on the burner controller imme-
diately after the power to the burner controller has been turned OFF. There is a
danger of electric shock because terminals F and G retain a charge for up to 1
minute after the power has been turned off.
Do not use this device with the cover removed. Doing so may result in an elec-
tric shock. If the cover has been removed from this device, be sure to reattach it
and tighten the four mounting screws completely before use.
CAUTION
Mounting, wiring, inspection, adjustment, maintenance etc., should be carried
out by a trained and experienced technician with knowledge and technical
skills related to combustion equipment and flame safeguard control devices.
The service life of the tube unit and shutter unit components of this device is
a maximum of 3years. To ensure operational safety, be sure to replace them
with new ones within the service life period. For replacement, use the AUD
Maintenance Kit (AUD60A1000), which includes the tube and shutter units.
Periodic inspection
(1) Turn off the power to the burner controller.
(2) Clean the monitoring window and monitoring pipe periodi-
cally.
Remove the device from the monitoring pipe and clean the
inside of the monitoring pipe and the quartz glass with a clean
cloth.
(3) To check the function of the tube unit, periodically conduct a
safety shutoff test.
Advanced Ultraviolet Burner Controller Model AUR300C
User’s Manual, No. CP-SP-1142E
Advanced Ultraviolet Burner Controller with
Communications Model AUR350C Users Manual, No. CP-
SP-1175E
Dynamic Self-Checking Burner Controller Model
AUR450C Users Manual, No. CP-SP-1264E
(4) Adjust the burner so that it operates properly as recommended
by the burner manufacturer.

Other manuals for Azbil AUD300C1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Azbil AUD300C1000 and is the answer not in the manual?

Azbil AUD300C1000 Specifications

General IconGeneral
BrandAzbil
ModelAUD300C1000
CategorySecurity Sensors
LanguageEnglish

Related product manuals