1
Chapter 1.
OVERVIEW
Overview
The AUD300C1000 Advanced Ultraviolet Flame Detector (hereafter
this/the device) is designed to detect ultraviolet radiation from an oil
or gas burner flame, for use with both batch and continuous operation
burners. The AUD300C1000 is used in combination with a dedicated
burner controller. By means of the built-in shutter, any malfunction
of the UV flame detector or burner controller is detected by the start
check and continuous self-checking function (Dynamic Self-Check),
ensuring highly reliable combustion safety control.
Features
• Maintenance parts such as the tube unit and shutter unit can be
handled as a single unit. This ensures easy replacement and mainte-
nance work.
• As for a flame sensor for the self-check, this unit is compact and
lightweight. This ensures free burner mounting.
• The operating ambient temperature is 100°C (up to 120°C during
flame detection) and the protection structure is IP66. This ensures
excellent environment proof performance.
• Because it can be mounted vertically and has a maximum wire
length of 200m, flexible installation is possible.
Names of parts
zMain unit
Model selection table
Model No. Lens type Description
AUD300C1000 Standard None
AUD300C100D Inspection report
AUD300C100T Tropicalization treatment
AUD300C100Y Traceability certificate
AUD300C100DT Inspection report + tropicalization treatment
AUD300C100YT Traceability certificate + tropicalization treatment
AUD300C1100 Condenser None
AUD300C110D Inspection report
AUD300C110T Tropicalization treatment
AUD300C110Y Traceability certificate
AUD300C110DT Inspection report + tropicalization treatment
AUD300C110YT Traceability certificate + tropicalization treatment
Mounting nut Flange unit: 81446924-001 or -101
AUD Maintenance Kit
AUD60A1000
Cover
Lead wires
Cover mounting screws (4)