Chapter 5. Trial Operation and Adjustment
Incorrect flame detector mounting angle (AUR355C)
Dirty flame detector sensing surface (AUR355C)
Tube unit deterioration (AUR355C)
Incorrect flame rod installation (AUR355B)
Area in contact with flame is insufficient.
Position of flame rod in flame is incorrect.
The flame rod insulator is at a high temperature (315°C).
Flame rod is affected by the ignition transformer.
If the ignition transformer is close to terminal F of the flame rod, electrons
in the flame will be absorbed into the ignition transformer, and as a result,
sufficient flame voltage will not be achieved.
The voltage can be checked on the 7-segment display or by connecting a flame
meter to terminals 25 & 26 on the front connector. It is necessary to obtain a
monitor/communication connector (81447514-001) to connect the FSP136A100
and the AUR355.
Analog ame meter:
FSP136A100
Flame voltage
display
Handling Precautions
For the flame voltage output signal wires, use 600 V PVC-insulated cable (IEC
60227-3), 0.75 mm
2
or more in cross-sectional area. The wiring should be no
longer than 10 m.
The input impedance of a measuring instrument used with this device must
be 100 kΩ or more.