Chapter 1. Overview
Most important points for ensuring safety
Design the equipment observing the following points to ensure safety.
If loads are driven by this device, connect the loads directly to this device.
Make sure that the start check runs correctly at startup.
Do not add a bypass circuit that allows manual operation of any load.
Both the main valve and pilot valve must have redundant shutoffs.
Precautions for system design
Provide a purge function with external instrumentation, taking into account factors
such as the conditions for purge and the time settings.
Model No.
The dedicated sub-base, sideboard, and front connector are not included with this
device. Please order them separately.
Basic
model No.
Flame
sensor
Flame
sensitivity
Flame
response
Power
voltage
(Reserved) (Reserved) Other Description
AUR355
B Flame rod
C UV flame detector
1 Standard
3 4 s max. (nominal: 3 s)
* 2 2 s max. (nominal: 1.5 s)
1 100 V AC
2 200 V AC
3 220 V AC
0
0
0 Without inspection data
*AUR355C only
D With inspection data

Other manuals for Azbil AUR355