5-65
Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
Operation type
The operation type of the internal event can be set.
Item (Bank) Display Contents Initial value User level
Internal Event 1 
Configuration 1  
(Event Configuration bank)
0: No event
1: PV high limit
2: PV low limit
3: PV high/low limit
4: Deviation high limit
5: Deviation low limit
6: Deviation high/low limit
7: Deviation high limit 
  (Final SP reference)
8: Deviation low limit 
  (Final SP reference)
9: Deviation high/low limit 
  (Final SP reference)
10: SP high limit
11: SP low limit
12: SP high/low limit
13: MV high limit
14: MV low limit
15: MV high/low limit
16: CT1 heater burnout/over-current
17: CT1 heater short-circuit
18: CT2 heater burnout/over-current
19: CT2 heater short-circuit
20: Loop diagnosis 1
21: Loop diagnosis 2
22: Loop diagnosis 3
23: Alarm (status)
24: READY (status)
25: MANUAL (status)
26: RSP (status)
27: During AT execution (status)
28: During SP ramp (status)
29: Control direct action (status)
30:  ST setting standby (status)  
(Invalid in this unit.)
31:  During estimated position control 
(status)
32: Timer (status)
33:  High and Low limits of MFB value 
(Invalid in this unit)
0 Basic, 
Standard, 
High function
Internal Event 2 
Configuration 1 
(Event Configuration bank)
0
Internal Event 3 
Configuration 1  
(Event Configuration bank)
0
Internal Event 4 
Configuration 1 
(Event Configuration bank)
0
Internal Event 5 
Configuration 1 
(Event Configuration bank)
0
Internal Event 6 
Configuration 1 
(Event Configuration bank)
0
Internal Event 7 
Configuration 1 
(Event Configuration bank)
0
Internal Event 8 
Configuration 1 
(Event Configuration bank)
0
  Handling Precautions
•  If ROM version 1 of the instrument information bank (
I
d02
) is prior to 
2.04, “33” cannot be set as [Internal Event configuration 1 operation type].