Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
  Handling Precautions
•  Do not allow the current to exceed the upper limit of the CT input display 
range. Doing so might cause a malfunction.
•  If a current exceeding the upper limit of the CT input display range is detected, 
the CT input failure alarm (
AL
1
1
) is displayed. However, if the excessive 
current is very large, the CT input failure alarm is not displayed.
•  The CT input display range and measurement current range change according 
to the number of CT turns and the number of CT power wire loops. Set for 
the number of CT turns and the number of CT power wire loops suitable for 
the conditions of the CT connected. The display range and the measurement 
current range are calculated by the formulas shown below. (The internal 
calculations of this device have an error of less than 0.1A.)
Display range lower limit (A) = 0.0 
Display range upper limit (A) = Number of turns ÷ (16 × number of power 
wire loops) × 1.4 
Measurement current range lower limit (A) = Number of turns ÷ (2000 × 
number of power wire loops)  
Measurement current range upper limit (A) = Number of turns ÷ (16 × 
number of power wire loops)
The table below shows examples of how display range and measurement 
current range change according to the number of CT turns and the number of 
CT power wire loops. Measurement current range is shown in parentheses.
Number of 
turns
Number 
of power
 
wire loops
100 turns 400 turns 800 turns 1600 turns 4000 turns
1 time
0.0 to 8.7A 
(0.1 to 6.2A)
0.0 to 35.0A
 
(0.2 to 25.0A)
0.0 to 70.0A
 
(0.4 to 50.0A)
0.0 to 140.0A
 
(0.8 to 
100.0A)
0.0 to 350.0A
 
(2.0 to 
250.0A)
2 times
0.0 to 4.3A 
(0.1 to 3.1A)
0.0 to 17.5A
 
(0.1 to 12.5A)
0.0 to 35.0A
 
(0.2 to 25.0A)
0.0 to 70.0A
 
(0.4 to 50.0A)
0.0 to 175.0A
 
(1.0 to 
125.0A)
6 times
0.0 to 1.4A 
(0.1 to 1.0A)
0.0 to 5.8A
 
(0.1 to 4.1A)
0.0 to 11.6A
 
(0.1 to 8.3A)
0.0 to 23.3A
 
(0.2 to 16.6A)
0.0 to 58.3A
 
(0.4 to 41.6A)
•  If ROM version 1 of the instrument information bank (
I
d02
) is prior to version 
2.04, the operation is always performed on the basis of 800 CT turns and one 
CT power wire loop. The number of 
CT
1
/
CT2
 turns and power wire loops is 
not displayed and cannot be set. 
•  If ROM version 1 of the instrument information bank (
I
d02
) is prior to version 
2.04, the CT input failure alarm (
AL
1
1
) is not displayed.