Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
Temperature unit
When the PV input range type is thermocouple or RTD, the temperature unit can 
be selected.
Item (Bank) Display Contents Initial value User level
Temperature unit 
(Setup bank)
0: Celsius (˚C) 
1: Fahrenheit (˚F).
0 Basic, 
Standard, 
High function
•  When the PV input range type is thermocouple or RTD, the display and setting 
can be configured.
Cold junction compensation (T/C)
When the PV input range type is thermocouple, either of the following can be 
selected:
• The cold junction compensation (T/C) is performed inside this unit.
• The cold junction compensation (T/C) is not performed inside this unit since 
an external cold junction compensation unit, such as ice bath is used.
Item (Bank) Display Contents Initial value User level
Cold junction 
compensation (T/C)(Setup 
bank)
0:  Cold junction compensation (T/C) is 
performed (internal).
1:  Cold junction compensation (T/C) is not 
performed (external).
0 High function
• When the PV input range type is thermocouple, the display and setting can be 
configured.
PV square root extraction dropout
When the PV input range type is DC voltage or DC current, a dropout value can be 
set so that the result of the PV square root extraction used to convert the pressure 
(differential pressure) into the flow becomes "0".
Item (Bank) Display Contents Initial value User level
PV square root extraction 
dropout (Setup bank)
0.0%: Square root extraction is not 
performed.
0.1 to 100.0%
0.0% High function
•  When the PV input range type is DC voltage or DC current, the display and 
setting can be made.
•  Details of PV square root extraction 
The calculation input in % and the calculation result in % are expressed as PVin 
and PVout, respectively. 
When the PV input is the PV square root extraction dropout set value or more 
and less than 100.0%, the control formula becomes as shown below.
PVout = √ PVin/100 X 100
When the PV input is larger than 0.0% and smaller than the PV square root 
extraction dropout set value, PVout = 0.0%. 
When the PV input is 0.0% or less or 100.0% or more, the square root extraction 
is not performed.  Therefore, PVout = PVin.