5-22
Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank) Display Contents Initial value User level
Cool-side proportional 
band (PID 8)
Same as PID 1
5.0% Basic, 
Standard, 
High function
Cool-side integration time 
(PID 8)
120s
Cool-side derivative time  
(PID 8)
30s
Cool-side MV low limit 
(PID 8)
Same as PID 1
0.0% Standard, 
High function
Cool-side MV high limit 
(PID 8)
100.0%
•  When the control method is other than the ON/OFF control (
CtrL
 ≠ 0), the 
display and setting can be configured.
•  [... for cool side] related items can be displayed and set when [
C26
: Heat/Cool 
control] is set to [1: Enabled].
•  When the Integration time (
I
-
-
) is set at “0s” or Cool-side integration time 
(
I
-
-
C
) is set at “0s” in the Heat/Cool control, no integration control action is 
performed.  The Manual reset (
rE-
-
) can be used in both the heat and cool 
controls.
•  Parameter settings for the cool control are displayed only when the Heat/Cool 
control is set enabled.
•  When the Integral time for heat side or cool side is "0s", the operation is 
processed with both Integral time for heat side and cool side  set at "0s".
•  If the setting is made so that the output low limit is greater than the output high 
limit, the operation is performed with the low limit swapped for the high limit 
automatically.
•  Priorities for PID group change 
Priorities for PID group change are shown below.
DI function
When PID group
change is
selected.
Zone function
During use
Low
During RSP
[SP group linked]
[RSP dedicated
group selectable]
SP group
assignment of
PID group
> > >
  Handling Precautions
•  If PID group change is used for an internal contact (DI), zone PID does 
not function. When zone PID is used, do not use PID group change by 
selecting PID group selection as the function of an internal contact (DI).