Direct fog ejections are requested using this button .
This operation is carried out immediately, provided that:
a) the fire status is not active, see p. 8
b) the not active, see p. 29.fog-isolation is
24
Before carrying out :a fog ejection
- Notify all persons in the vicinity of the area
- Notify the fire controller in the building (PAC fire alert).
- You will use a cartridge, so make sure you have a replacement.
To comply with security industry good practice and professionalism,
always conduct a full system test after the installation of a system to
confirm its correct operation and performance.
A forced fog ejection only indicates that the fog generating
component of the fog generator is functioning properly.
This test does not confirm the correct wiring, control inputs or
settings of the controller.
Forcing a fog ejection:
Force ejectionForce ejectionForce ejection
p. 30 - Fog ejection control
F
F
!
BANDIT Controller CF31 v2 / Manual v.102