EasyManua.ls Logo

Bandit CF31 - Page 35

Bandit CF31
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description:
Alarm panel connections:
- 12 V supply: possibly through fuse 1AT (slow).
- Monitoring output: the output relay is open as long as the alarm panel
is not monitoring and closed as long as it is in monitoring status.
- Alarm output: the output relay is open as long as the alarm panel is not
in an alarm condition and switches to closed when in alarm.
- Tamper: Tamper is detected when the loop is interrupted.
- Dialler input 1: OKout output: Technical failures / problems are reported
to the dialler when NO contact opens.
- Dialer input 2: Empty fog cartridge or "no power to fog generator".
Both problems are reported together to the dialler when one or both
NO contact ([Empty] or [Power]) opens.
Dip switch settings:
Dip G: is ON = the controller and the fog generator are in
monitoring mode as long as there is 12 VDC provided to
the Guard input [Guard].
As long as the controlling alarm system's monitoring
contact closes, the orange Guard LED will light
and BANDIT is in monitoring mode .
Dip A: is ON = the controller and the fog generator are in alarm mode
(Incl. fog ejection) as long as there is 12 VDC provided to the alarm
input [Alarm].
So when the alarm system closes its alarm contact, the orange
Alarm LED will light and BANDIT remains in alarm mode until
removal of monitoring mode.
Dip C: is OFF = the confirmation input is not connected, so there is never
going to be 12 VDC on the confirmation input [Conf.]. The controller
thus receives continuous acknowledgement to switch to alarm mode.
Dip F: is ON = the fire input is not connected, so there is never going to be
12 VDC on the Fire input [Fire]. So the fire input is never active to thus
prevent a fog ejection.
Dip switch block M³ is OFF-ON-ON as an example, the fog generator is
programmed for a fog ejection and associated cartridges of 100 to 120 m³
(See p. 23).
Guard
G+ G-
Alarm
A+ A-
1 2 3 4 1 2 3 1 21 2 3 4 1 2 3 1 2
Front
Inputs
G
A
C
F
2
3
X1
1 2 3 4 1 2 3 1 2
Installation example 1 - p. 33
GuardGuard
BANDIT Controller CF31 v2 / Manual v.102