5
3.3 Connections
The following points must be followed for the 12V connections:
We strongly recommend using a 12V lead gel rechargeable battery for this
device. Other rechargeable battery types can also be used, but only after taking
into account the end-of-charge voltage. A fuse that corresponds to the cable
cross-section must be installed in the battery cable.
The controllers are designed to operate using 12V DC. The pumps and valves to
be connected must be designed for this voltage!
The earth connections (M) are electrically connected and are not switched!
The switching output (A1) is electronic 12V DC N/O contact. A potential-free
changeover contact is switched parallel to the output.
3.4 Temperature sensor connection
The SOLAREG II BASIC DC devices use PT1000 precision platinum temperature sen-
sors. 2 sensors are required, the third sensor is optional.
Mounting / wiring the temperature sensors:
Mount the sensors on the collector and the storage tank. Ensure proper heat
transfer and use heat-conducting paste if necessary.
Cross-sections for cable extensions (shielded):
- up to 15m 2 x 0.5mm
2
,
- up to 50m 2 x 0.75mm
2
.
Connect the temperature sensors according to the system diagram. The polarity
of both conductors for the temperature sensors is irrelevant.
Sensor cables must be laid separately from 230V wires.
Sensor connection boxes equipped with surge protection should be used for
collector sensors and cable extensions.
4 Short descriptions and device operation
4.1 Display layout
During actual operation, these symbols are only displayed for selection once
depending on the menu position.
Active menu in the menu levels
Allocation of the current display
Current measured values, times or control-
ler states: herr 59.6C°.
Measuring point
Controller state/messages
Display symbols
All possible display symbols are
shown below.
ok?
hPa
start
%
stopdTmin max
F