DGC-2020ES BESTlogic™Plus
Name
Description
Symbol
Status Input
Global Low
Coolant Level
True when the Low Coolant Level input is true.
Status Input
Ground Delta
Override
True when the Grounded Delta Override input is
true.
Status Input
Idle Request
True when the Idle Request logic element is true.
Status Input
In Alarm State
True when the DGC-2020ES is in the alarm state.
Status Input
In Connecting
State
True when the DGC-2020ES is in the connecting
state.
Status Input
In Cooling State
True when the DGC-2020ES is in the cooling state.
Status Input
In Cranking
State
True when the DGC-2020ES is in the cranking state.
Status Input
In Disconnect
State
True when the DGC-2020ES is in the disconnect
state.
Status Input
In Prestart State
True when the DGC-2020ES is in the pre-start state.
Status Input
In Pulsing State
True when the DGC-2020ES is in the pulsing state.
Status Input
In Ready State
True when the DGC-2020ES is in the ready state.
Status Input
In Resting State
True when the DGC-2020ES is in the resting state.
Status Input
In Running
State
True when the DGC-2020ES is in the running state.
Status Input
Lamp Test
True when the Lamp Test logic element is true or
the Lamp Test button is pressed on the front panel.
Status Input
Load Take Over
True when the Load Take Over logic element is true.
Status Input
Low Line
Override
True when the Low Line Override input is true.
Status Input
Mains Breaker
Status
True when the mains breaker is closed.
Status Input
Mains Fail Test
True when the Mains Fail Test logic element is true.