13-16 9469200995
BESTlogic™Plus DGC-2020ES
Name
Description
Symbol
Generator
Protection
50
True when the 50 element is configured as a pre-
alarm and has tripped.
Generator
Protection
81 Over
True when the 81 Over element is configured as a
pre-alarm and has tripped.
Generator
Protection
81 Under
True when the 81 Under element is configured as a
pre-alarm and has tripped.
Global Pre-
Alarm
True when one or more pre-alarms are set.
Heating for
Exhaust Regen
A manual or automatic exhaust regeneration request
has occurred, but the exhaust system is not hot
enough for regeneration to occur. The ECU feeds
fuel into the exhaust stream to increase the
temperature to accomplish regeneration.
Hi Coolant
Temp
True when the High Coolant Temp Pre-Alarm
threshold has been exceeded.
High Exhaust
Temperature
True when Diesel Particulate Filter (DPF) lamp
status broadcast over CAN Bus indicates high
exhaust temperature.
High Fuel Level
True when the High Fuel Level Pre-Alarm settings
have been exceeded.
Inter Generator
Comm Fail
True when the DGC-2020ES detects that an
individual generator previously connected to a
generator network has lost connection.
Isuzu DEF Low
Refill DEF
True when an Isuzu engine ECU has detected low
DEF level and has indicated the DEF symbol should
be displayed.
Isuzu Forced
Purge Request
True when a forced purge has been requested by
momentarily pressing the Manual Regeneration
button or setting the DPF Regen setting on the front
panel, or setting the DPF Manual Regenerate button
in BESTCOMSPlus.
Isuzu SCR
Forced Purge
True when a forced purge is in progress after having
been requested.
Isuzu SCR
Purge
True when a normal SCR Purge is in progress.
Normal purges occur during normal operation if the
engine load is sufficient to allow purge to occur.
Isuzu Service
Tool Forced
Purge Request
True when a forced purge has been requested
through the Isuzu Service Tool. This will remain true
until the forced purge cycle begins.
Low Battery
Voltage
True when the Low Battery Voltage Pre-Alarm
settings have been exceeded.
Low Coolant
Level
True when the Low Coolant Level function is
configured as a pre-alarm and the activation delay
has expired. In addition, true when CAN Bus is
enabled and the Low Coolant Level Pre-Alarm
threshold has been exceeded.