13-18 9469200995
BESTlogic™Plus DGC-2020ES
Service Tool
Forced
Regenerate
A manual or forced regeneration is in progress and
was initiated from a manufacturer’s service tool. This
indication is received from the engine ECU over
J1939 CAN Bus as SPN 4175 Diesel Particulate
Filter Active Regeneration Forced Status or SPN
6934 SCR System Cleaning Forced Status. When
the value is 2, a Service Tool Forced Regenerate
pre-alarm is annunciated.
Switch Forced
Regenerate
A manual or forced regeneration is in progress and
was initiated from a manual regeneration switch.
This indication is received from the engine ECU over
J1939 CAN Bus as SPN 4175 Diesel Particulate
Filter Active Regeneration Forced Status or SPN
6934 SCR System Cleaning Forced Status. When
the value is 1, a Switch Forced Regenerate pre-
alarm is annunciated.
Torque Limit True while the engine is running in a reduced torque
mode due to exhaust system issues such as Low
DEF, Purge Required, Exhaust System Error, etc.
This reflects the status of the exhaust system
Torque Limit lamp, which is communicated from the
Engine ECU to the DGC-2020ES via J1939 CAN
Bus communications.
Torque Limit
Severe
True while the engine is running in a severely
reduced torque mode due to exhaust system issues
such as Low DEF, Purge Required, Exhaust System
Error, etc. This reflects the status of the exhaust
system Torque Limit lamp, which is communicated
from the Engine ECU to the DGC-2020ES via J1939
CAN Bus communications.
Sensing Fail
True when the Voltage Sensing Fail is configured as
a pre-alarm and the activation delay has expired.
True when the Weak Battery Voltage Pre-Alarm
settings have been exceeded.
Sender Fail
True when the Coolant Temp Sender Fail is
configured as either a pre-alarm or alarm and the
activation delay has expired.
Sender Fail
True when the Fuel Level Sender Fail is configured
as either a pre-alarm or alarm and the activation
Sender Fail
True when the Oil Pressure Sender Fail is
configured as either a pre-alarm or alarm and the
activation delay has expired.
Fail
True when the Speed Sender Fail activation delay
has expired.
Sensing Fail
True when the Voltage Sensing Fail is configured as
either a pre-alarm or alarm and the activation delay
has expired.