13-20 9469200995
BESTlogic™Plus DGC-2020ES
Name
Description
Symbol
XNOR
Input
Output
0
0
1
0
1
0
1
0
0
1
1
1
When an XNOR gate has more than two inputs, the output is true
whenever an even number of inputs are true. The output is also true if
no inputs are true.
NOT
(INVERTER)
Input
Output
0
1
1
0
Pickup and Dropout Timers
Drop Out
Timer
Used to set a delay in the logic.
For more information, refer to Programming BESTlogicPlus, Pickup
and Dropout Timers, later in this section.
Pickup Up
Timer
Used to set a delay in the logic.
For more information, refer to Programming BESTlogicPlus, Pickup
and Dropout Timers, later in this section.
Latches
Reset Priority
Latch
When the Set input is on and the Reset input is off, the latch will go to
the SET (ON) state. When the Reset input is on and the Set input is
off, the latch will go to the RESET (OFF) state. If both the Set and
Reset inputs are on at the same time, a reset priority latch will go to the
RESET (OFF) state.
Set Priority
Latch
When the Set input is on and the Reset input is off, the latch will go to
the SET (ON) state. When the Reset input is on and the Set input is
off, the latch will go to the RESET (OFF) state. If both the Set and
Reset inputs are on at the same time, a set priority latch will go to the
SET (ON) state.
Other
Comment
Block
Enter user comments.
Elements
This group contains elements for the 27, 47, 50, 59, and 81. It also contains elements for Generator
Breaker, Mains Breaker, Logic Alarm, Logic Pre-Alarm, Configurable Elements, AUTO Mode, OFF Mode,
RUN Mode, Run with Load, Engine Run, ATS, Run Inhibit, Test Inhibit, Pre-Start Output, Start Output,
Run Output, Cool Stop Request, Cool Down Request, External Start Delay, Start Delay Bypass, Alternate
Frequency Override, Mains Fail Test, Load Take Over, EPS Supplying Load, MTU Speed Demand
Switch, Reset, Alarm Silence, Lamp Test, Idle Request, Low Fuel Pre-Alarm, Diesel Particulate Filter
Manual Regeneration, Diesel Particulate Filter Regeneration Inhibit, Emergency Stop, Speed Raise,
Speed Lower, MTU Cylinder Cutout Disable, and Automatic Breaker Operation Inhibit from PLC.