3-5
Figure 3-4. Brush Type Rotary Exciter Interconnection.
(2) When the generator output voltage is different than the preceding values and exceed the values
specified in Table 1-2, a power transformer must be used to match the generator voltage to the
regulator input. If excessive voltage is applied to the regulator input (terminals 3 and 4), the regulator
may be damaged.
CAUTION
Without the use of this transformer, a ground at any point in the field
circuit and another ground in the generator output, could result in
failure of the regulator.