Schaffner FN 3120H-80-35
for active mains inverter
BM4
135
FN 3120H-150-40
for active mains inverter
BM4145
FN 3100-300-99
for active mains inverter
BM4163
Max.
supply voltage
3 x 480 V
AC
+10 %,
50/60 Hz
3 x 480 V
AC
+10 %,
50/60 Hz
3 x 480 V
AC
+10 %,
50/60 Hz
Rated current
(at T
B
= 50 °C)
80 A 150 A 300 A
Peak current
(at T
B
= 50 °C)
1,5 x I
N
for < 1 min per hour
1,5 x I
N
for < 1 min per hour
1,5 x I
N
for < 1 min per hour
Test voltage Cable - Cable: 2250 V
DC
/ 2 s
Cable - Cabinet: 2750 V
DC
/ 2 s
Connection L1/L2/L3: safe-to-touch
sc
rew contact
PE: Bolt M10
L1/L2/L3: safe-to-touch
screw contact
PE: Bolt M10
L1/L2/L3: safe-to-touch
screw contact
PE: Bolt M12
Maximum
connection cross-
sect
ion
50 mm
2
95 mm
2
150 mm
2
Protection class IP 20 IP 20 IP 20
Electrical data
Instruction handbook Mains filters BFN
Document No.: 5.09010.03 Baumüller Nürnberg GmbH
30
of 70
3.4

Table of Contents