DANGER!
Risk of fatal injury due to
high leakage current!
The cross-section of the protective gr
ound conductor must be at least 10 mm²
(EN 61800-5-1, Chapter 4.3.5.5.2).
BFN 3-1- ... -001 0007 0016 0030 0042 0056 0075 0100 0130
Max. power supply voltage 3 x 480 V
AC
+10%, 50/60 Hz
Rated current (at T
B
= 40 °C) 7.6 A 17.5 A 33 A 46 A 70 A 82 A 109 A 142 A
Rated current (at T
B
= 50 °C) 7 A 16 A 30 A 42 A 56 A 75 A 100 A 130 A
Peak current 1.5 x I
N
for < 1 min per hour
Max. voltage
Outer conductor/GND
Neutral point of the outer conductor/GND
305 V
AC
0 V
Max. test voltage line to line
line to case
2.1 kV
DC
for 2 s at 25 °C
2.7 kV
DC
for 2 s at 25 °C
Maximum connection cross-section 4
mm²
4
mm²
10
mm
²
10
mm²
16
mm²
25
mm²
50
mm²
50
mm²
Power loss (typical) 4 W 8 W 12 W 15 W 18 W 24 W 24 W 30 W
Harmonic frequencies (mains voltage) THD
U
< 10%
Protection rating IP 20
Weight 0.6 kg 1.0 kg 1.3 kg 1.6 kg 1.9 kg 2.6 kg 4.0 kg 4.2 kg
BFN 3-1-... -001
002
0
EPCOS
B84143A0150R410
LGF
FFU 3x295AB-SBM
Max. power supply voltage 3 x 480 V
AC
+10 %, 50/60 Hz
Rated current (at T
B
= 40 °C) 20 A 150 A 295 A
Peak current (at T
B
= 40°) 1.5 x I
N
for < 3 min per hour
1.5 x I
N
for < 60 s per hour
Max. voltage
outer conductor/GND
neutral point of the outer conductor/GND
305 V
AC
0 V
Max. test voltage at 25 °C
line to line
line to case
2.1 kV
DC
at 25 °C for 2 s
2.2 kV
DC
for 2 s
2.7 kV
DC
for 2 s
2.1 kV
DC
for 2 s
2.7
kV
DC
for 2 s
Maximum connection cross-section 95 mm²
Harmonic frequencies (mains voltage) THD
U
< 10 %
Protection rating IP 20
Weight 13.5 kg
Accessories and spare parts
Instruction handbook b maXX 5000
Document No.: 5.09021.16
273